| 加工定制:否 | 品牌:YOKOGAWA/横河 | 型号:ADV161-P00 |
| 测量范围:1 |
ADV161输入模块日本横河
|
| 描述 |
型号 | ADV161 | 数字量输入模块(64通道,24 V DC,隔离) |
后缀代码 | -P | 按钮输入 |
5 | 没有状态显示;没有防爆保护 | |
E | 没有状态显示;有防爆 | |
0 | 基本型 | |
1 | 与ISA标准的G3选项 |
ADV161数字量输入模块型号组合:
ADV161-P50 ADV161-PE0 ADV161-P51 ADV161-PE1
Digital Input Modules
The Digital Input Modules receive32-channel or 64-channel 24 V DC ON/OFF signals.
The ADV151 and ADV161 can be used indual redundant configuration.
Item | Specifications | ||||
Model | ADV151-P/ADV151-E (*1) | ADV157 | ADV161 | ||
Number of input channels | 32 | 32 | 64 | ||
Rated input voltage (*2) | 24 V DC (sink/source) | 24 V DC (sink/source) | 24 V DC (sink/source) | ||
Input ON voltage | 18 to 26.4 V DC | 18 to 26.4 V DC | 20 to 26.4 V DC | ||
Input OFF voltage | 5.0 V DC or less | 5.0 V DC or less | 5.0 V DC or less | ||
Input current (at rated input voltage) | 4.1 mA±20 % / channel | 4.1 mA±20 % / channel | 2.5 mA±20 % / channel | ||
Maximum allowable input voltage | 30.0 V DC | 30.0 V DC | 30.0 V DC | ||
Withstanding voltage | Between input signal and system: 2 kV AC, For 1 minute Between commons: 500 V AC, For 1 minute, common every 16-channel (*3) | ||||
Functions Status input
Pushbutton input |
Function for detecting ON/OFF status Function for detecting pushbutton edges |
Function for detecting ON/OFF status — |
Function for detecting ON/OFF status Function for counting the pushbutton edges | ||
Input response time | 8 ms or less (for status input) | ||||
Minimum ON detection time | 20 ms (for pushbutton input) | ||||
Maximum ON/OFF cycle | 25 Hz (for pushbutton input) | ||||
Maximum current consumption | 500 mA (5 V DC) 350 mA (5 V DC) 550 mA (5 V DC) | ||||
Weight | 0.3 kg | 0.4 kg | 0.3 kg | ||
External connection | Pressure clamp terminal,Dedicated cable (AKB331),MIL connector cable | Pressure clamp terminal | Dedicated cable (AKB337),MIL connector cable | ||
*1: OnlyADV151-P is allowed to be installed in the remote node. ADV151-E is not allowedto be installed in the remote node.
*2: ADV151,ADV157 and ADV161 are common every 16-channel. All voltage input signals to beconnected (24 V DC) must be in the same polarity.