FIO System Overview
TheFIO is an I/O system that is connected to a control station via ESB or ER bus.
FIOconsists of two types of node units on two types of buses. The node units on anESB bus referred to as local nodes, and those on an ER bus referred to asremote nodes. Each of these nodes is composed of a base unit, power supplymodule, bus interface module, and input/output modules.
Powersupply module, bus interface module, and input/output modules can be configuredredundantly.
Anexample of system configuration is shown below.
Item | Specification | |
Ambient temperature | Normal operating | 0 to 50 °C (Local Node, Compact Field Control Unit (for FIO))0 to 60 °C (Remote Node Standard)(-20 to 70 °C temperature option for Remote Node) (*1) |
Transporting/storing | -20 to 60 °C (avoid direct sunlight.)(-40 to 85 °C temperature option for Remote Node, avoid direct sunlight) | |
Ambient humidity | Normal operating | 5 to 95 %RH (should have no condensation.) |
| Transporting/storing | 5 to 95 %RH (should have no condensation.) |
Ambient temperature change rate | Normal operating | Within ±10 °C/h |
| Transporting/storing | Within ±20 °C/h |
Power supply | Voltage range | 100 to 120 V AC ±10 % |
220 to 240 V AC ±10 % | ||
24 V DC ±10 % | ||
Frequency | 50/60 ±3 Hz | |
Distortion factor | 10 % or less | |
Peak value | 125 V or more (100 V system) | |
274 V or more (220 V system) | ||
Instantaneous power failure | 20 ms or less (when receiving rated AC voltage) | |
DC power supply ripple rate | 1 % p-p or less | |
Grounding | 100 ohms or less, Independent grounding | |
Dust | 0.3 mg/m3 or less | |
Corrosive gas | ANSI/ISA S71.04 G2 (standard) (ANSI/ISA S71.04 G3 option) | |
Vibration | Continuous vibration | Displacement amplitude 0.25 mm or less (1 to 14 Hz) Acceleration 2.0 m/s2 or less (14 to 100 Hz) |
Earthquake | Acceleration 4.9 m/s2 or less | |
Transport vibration | Horizontal 4.9 m/s2 or less, vertical 9.8 m/s2 or less (packed state) | |
Shock | Transport shock | Horizontal 49.0 m/s2, vertical 98.0 m/s2 (packed state) |
Noise | Electric field | 3 V/m or less (26 MHz to 1.0 GHz)3 V/m or less (1.4 to 2.0 GHz)1 V/m or less (2.0 to 2.7 GHz) |
Magnetic field | 30 A/m or less (AC), 400 A/m or less (DC) | |
Static electricity | 4 kV or less (contact discharge), 8 kV or less (aerial discharge) | |
Altitude | 2000 m or less | |
*1: When a remote node is used under thetemperature environment (-20 to 0 °C), it requires 10minutes to start up EB501 after turning on the power switch.
When the following modules are installed in a remote node, the ambienttemperature should be 0 to 50 °C.
AAP149, AAP849, ADV157, ADV557, ADV161, ADV561, ADV859, ADV159, ADV559,ADV869, ADV169, ADV569,ALR111, ALR121, ALE111, ALF111, ALP111
When AAI543-1 (fast response) is installed in a remote node, the ambient temperatureshould be 0 to 60 °C.