GENERAL
This document describes the general specifications of
the FCN-RTU low power autonomous controller.
For functions, refer to “FCN-RTU Low Power
Autonomous Controller Functions” (GS 34P02Q02-
01E).
FEATURES
• High performance and low power consumption
modular controller
• Memory with ECC.
• FCN-RTU can be used wide temperature range and
high altitude place.
• Analog and digital I/Os adequate for gas/oil wellhead
control built in CPU module
• Four serial ports for plural communications built in
CPU module
• Up to eight additional I/O modules (with NFBU200)
• Wide voltage range (10 to 30 VDC input) power
supply module (NFPW426)
• Power supply module can be duplexed (NFBU200
with NFPW444)
• Low heat dissipation eliminates the need for a fan
• A wealth of RAS features — CPU self-diagnostics,
temperature monitoring, I/O diagnostics, and more
• Additional I/O modules (except CPU embedded I/Os)
hot-swappable
FCN-RTU Low Power
Autonomous Controller
Hardware
Yokogawa Electric Corporation
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5616 URL:
GS 34P02Q13-01E
GS 34P02Q13-01E
©Copyright Dec. 2008(YK)
11th Edition May 12, 2014(YK)
F01E.ai
CONFIGURATION
FCN-RTU consists of the following modules:
• Base module (NFBU050,NFBU200)
• Power supply module (NFPW426,NFPW444)
• CPU (with built-in I/Os) module (NFCP050)
• Additional I/O modules (up to eight modules can be mounted on a base module)
There are two types of base module.
Short type : Configuration with a NFBU050 base module (short)
Long type : Configuration with a NFBU200 base module (long)
The following table shows a list of the functions of each configuration.
Table FCN-RTU Control Function List
Base module CPU Module Power supply module Power supply
Redundancy
Max number of mountable
I/O modules (*3)
NFBU050 base module (short)
NFCP050
NFPW426,NFPW444 N.A. 3 (*1)
NFBU200base module (long) NFPW444 8 (*2)
*1: Two from the five slots are exclusive for one CPU module.
*2: Two from the ten slots are exclusive for one CPU module.
*3: Available modules are limited. Please refer to “ ■ I / O module”.