| 加工定制:否 | 品牌:YOKOGAWA/横河 | 型号:ALR121-S00 |
| 工作电压:·V | 输出频率:·kHz | 产品认证:· |
Models ALR111, ALR121,ALE111 Subsystem Communication Module (for FIO)
ThisGS is hardware specifications of the Subsystem Communication Module (for FIO)that can be installed in the ESB Bus Node Unit (ANB10S, ANB10D), the ER BusNode Unit (ANR10S, ANR10D) (*1) and the Compact Field Control Unit (for FIO)(AFF50S, AFF50D, AFV10S, AFV10D) (*2).
*1: Requirements for installation ofcommunication modules in the ER Bus Node Unit. Communication modules can be installedin the ER Bus Node Unit when the firmware revision of EB401 is R3 or later andany one of the following is met.
• When the FCS model nameis AFG30, AFG40, AFG81, AFG82, AFG83 or AFG84 and the software revision is R3.03 or later.
• When the FCS model nameis AFF50 and the software revision is R3.04 or later.
• When the FCS model nameis AFV10 and the software revision is R3.05 or later.
*2: AFF50S and AFF50D are supported by R3.04or later, and AFV10S and AFV10D are supported by R3.05 or later.
ThisModule exchanges data with a subsystem such as a programmable controller via aserial communication line using the Subsystem Communication Package. It can be installedin the ESB Bus Node Unit, the ER Bus Node Unit and the Compact Field ControlUnit (for FIO).
Item | Specifications | |
Model | ALR111 | ALR121 |
Interface | RS-232C (2 ports) | RS-422/RS-485 (2 ports) |
How connected | Point-to-point | Point-to-point (RS-422) Multipoint (RS-485) |
How communicates | Half-duplex | |
How synchronizes | Start-stop synchronization | |
Communication speed | 1200/2400/4800/9600/19200/38400/57600/76800/115200 bps | |
Transmission code | ASCII/binary | |
Character length | 7/8 bits | |
Stop bit length | 1/2 bits | |
Parity check | None/even/odd | |
When a signal is received after data transmission | 1 ms | |
Transmission distance | Maximum 15 m | Maximum 1200 m (total extended length) |
How installed | Mounted in ANB10, ANR10, AFF50, AFV10 | |
I/O wiring | AKB131, AKB132, AKB133, and AKB134 cables, etc. | Cable with 3-pair shield, AKB161 or AKB162 |
Wiring connection | D-sub 9-pin (female x 2) | Clamped with terminal block’s M4 screws(5 poles x 2) |
Current consumption | 0.5 A | |
Weight | 0.3 kg | 0.3 kg |
ThisModule exchanges data with a subsystem such as PLC via an Ethernetcommunication line using the Subsystem Communication Package. It can beinstalled in the ESB Bus Node Unit, the ER Bus Node Unit and the Compact Field ControlUnit (for FIO).
Item | Specifications |
Model | ALE111 |
Physical Layer Interface | IEEE802.3 10BASE-T |
How connected | Point-to-point |
Connector | RJ-45 |
Communication speed | 10 Mbps |
Transmission distance | 100 m per segment |
Transmission route | 100 ohm twisted -pair cable (not shielded) |
Transmission distance | 100 m per segment |
No. of ports | One port |
Media access control | CSMA/CD |
Current consumption | 0.5 A |
Weight | 0.3 kg |
Numberof ALR111s, ALR121s, ALP111s, ALE111s per FCS:
Standard Field Control Station:Max.6 (*6) (3 pairs for a dual-redundant configuration)/FCS (*1)
Enhanced Field Control Station:Max.16 (8 pairs for a dual-redundant configuration)/FCS (*2)
Control Function for Compact FieldControl Unit (for FIO):
Max.8 (4 pairs for a dual-redundantconfiguration)/FCS (*3)
Control Function for Basic FieldControl Unit (for FIO, for Vnet/IP):
16 max. (*5) (8 pairs for adual-redundant configuration)/FCS (*4)
*1: AFS30□, AFS40□
*2: AFG30□, AFG40□, AFG81□, AFG82□, AFG83□,AFG84□
*3: AFF50□
*4: AFV10□
*5: When not using Application CapacityExpansion Package, the maximum total number is 8/FCS. For details, refer to“Control Function forBasic Field Control Unit (for FIO, for Vnet/IP)” (GS 33P03K10-31E).
*6: ALP111 cannot be installed in StandardField Control Station.
Number of ALR111s, ALR121s, ALP111s, ALE111s, ALF111 per ER bus train(*7):Max.8 per ER bus train
*7: The communication module (ALR111,ALR121, ALE111 and ALP111) can be installed to remote node only when the main memoryof the FCS is 32 MB.
|
| Description |
Model | ALR111 | RS-232C Communication Module (2-port, 1200 bps to 115.2 kbps) |
Suffix Codes | -S | Standard Type |
0 | Always 0 | |
0 | Basic Type | |
1 | With ISA Standard G3 option |
|
| Description |
Model | ALR121 | RS-422/RS-485 Serial Communication Module (2-port, 1200 bps to 115.2 kbps) |
Suffix Codes | -S | Standard Type |
0 | Always 0 | |
0 | Basic Type | |
1 | With ISA Standard G3 option |
|
| Description |
Model | ALE111 | Ethernet Communication Module |
Suffix Codes | -S | Standard Type |
0 | Always 0 | |
0 | Basic Type | |
1 | With ISA Standard G3 option |
Specifymodel and suffix codes.
• CENTUM is a registeredtrademark of Yokogawa Electric Corporation.
• Ethernet is aregistered trademark of XEROX Corporation.
• Other company andproduct names appearing in this document are trademarks or registeredtrademarks of their respective holders.