| 加工定制:否 | 品牌:YOKOGAWA/横河 | 型号:ALP111 |
| 工作电压:·V | 输出频率:·kHz | 产品认证:· |
ALP111 PROFIBUS-DP CommunicationModule
PROFIBUS-DPCommunication Module is designed to operate as PROFIBUS-DP master devices andexchange data with PROFIBUS-DP devices. This module can be installed on ESB busnode units (ANB10S or ANB10D), ER bus node units (ANR10S or ANR10D) (*1) orCompact field control units (for FIO) (AFF50S, AFF50D, AFV10S,AFV10D) (*2).
*1: In R3.07 or later, ALP111 modules can beinstalled in the ER bus node units (ANR10S or ANR10D).
*2: AFF50S and AFF50D are supported by R3.04or later, and AFV10S and AFV10D are supported by R3.05 or later.
PROFIBUSCommunication Package (LFS2452) is required to exchange data with PROFIBUS-DP devices.
Item | Specifications |
Model | ALP111 |
Interface | PROFIBUS-DP (upward compatibility with PROFIBUS-DP) |
Transmission specification | EIA-RS485-compliant |
Signal ***lation | ***lated |
Connector | D-sub 9 pin (female) (*1) |
Communication speed | 9600 bps to 12 Mbps |
Transmission route | Shielded |
Maximum transmission distance | 1.2 km per segment (when communication speed is 9600 bps) |
Number of ports | One port |
Maintenance port | D-sub 9 pin (male) Interface: RS-232C |
Maximum current consumption | 0.7 A |
Weight | 0.3 kg |
*1:Connector for PROFIBUS must comply with PROFIBUS Specification(PROFIBUS-Specification-Normative-parts-2).
ALP111modules can only be installed on control stations equipped with ControlFunction for Enhanced Field Control Station (for FIO) and Control Function forCompact Field Control Station (for FIO). These modules can be installed on ESBbus units (directly connected nodes), ER bus node units (ANR10S or ANR10D) orCompact Field Control Unit (for FIO).
Totalnumber of ALP111, ALR111, ALR121, and ALE111 modules:
Enhanced Field Control Station:Max.16 (8 pairs for a dual-redundant configuration)/FCS (*1)
Compact Field Control Unit (forFIO): Max. 8 (4 pairs for a dual-redundant configuration)/FCS (*2)
Basic Field Control Unit (for FIO,for Vnet/IP): Max.16 (*4) (8 pairs for a dual-redundant configuration)/FCS (*3)
*1: AFG30□, AFG40□, AFG81□, AFG82□, AFG83□,AFG84□
*2: AFF50□
*3: AFV10□
*4: When not using Application CapacityExpansion Package, the maximum total number is 8/FCS. For details, refer to GS 33P03K10-31E“Control Function for Basic Field Control Unit (for FIO, for Vnet/IP).”
|
| Description |
Model | ALP111 | PROFIBUS-DP Communication Module |
Suffix Codes | -S | Standard type |
0 | Always 0 | |
0 | Basic type | |
1 | With ISA Standard G3 option |
Specifymodel and suffix codes.
• CENTUM is a registeredtrademark of Yokogawa Electric Corporation.
• Other product andcompany names appearing in this document are trademarks or registeredtrademarks of their respective holders.